Supply Power SPD  

POE SPD


Ⅰ. Introduction
POE network surge protection device is designed, manufactured, and tested in compliance with international standard IEC61643.1, China national standard GB18802.1,And quality control of our product is in strict accordance with ISO9001.
It’s adopted in various kinds of low voltage devices like video devices, POE network switch, web camera and etc. It can prevent the devices from being damaged by induced over voltage and surge over current of the lightning strike.
Ⅱ. Features
◆Large discharge capacity, stable;
◆Low residual voltage, good protection;
◆Fast responding, nanosecond level;
◆Low insertion loss, good transmission
◆Easy installation and maintenance;
III. Technology parameters:

Model
JM-ES-RJ45
Protection Class:
Network signal
power
Nominal operating Voltage Un(V)
5V
48V
Maximum operating Voltage Uc(V)
6V
60V
Nominal Discharge Current(8/20μs)In(KA)
1KA
Max. Discharge Current (8/20μs)Imax(KA)
3KA
Line to Line Up(V)
15V
Line to Ground Up(V)
≤120V
Response Time(ns)
≤25ns
Transmission rate(bps)
1000M
Insertion Loss(dB)
≤0.5dB
Protected Core
1-8
Protection Mode
full protection
Interface Model
RJ45
Material of Outer Shell
Aluminum alloy
IP Rating ,IEC 60529/EN 60529 approved
IP20
Working Environment
Temperature:-40℃~+80℃,Relative Humidity<95%
Size(mm)
119*40*25

Ⅳ.Product Installation:
 1. This product is installed between signal channel and protected equipment, the output end is connected with protection equipment.
 2. All wirings must be solid and be connected by electric.
 3. The earth terminal of SPD should be connected to earth ground, ground screw with terminal forks which is applied to connect grounding collection row and earth terminal of SPD, after connecting the ground wire well, be sure to tighten the screws. The grounding line:
BVR ≥ 2.5mm2, the length of the ground wire to grounding collection row should be less than 1 m. Lightning proof grounding should be consistent with lightning protection regulatory requirements, grounding wire should be as thick and short as possible, resistance should be less than 10Ω.